Control cable NYCYRY (wire armoured with concentric conductor) 0.6/1 KV

 

Technical data:

- Power cable according to IEC 60502-1 , DIN VDE 0271 , ISIRI 3569

- Temperature range:

   flexing C°-5 to C°+50

   fixed installation C°-30 to C°+70

- Nominal voltage: U0/U=0.6/1 KV

- Test voltage a.c. , 50Hz : 4 KV

Cable structure:

- Cu / PVC / PVC / Cu / PVC / SWA / PVC

- Copper conductor class1 & 2 acc. to IEC 60228

- Insulation PVC/A

- Concentric conductor in inner layer of round copper wires ,outer layer with copper tape.

- Galvanised steel or aluminium wire armoured.

- Sheath  PVC/ST2 90°C

Application:

As control and connecting cable in machines, conveyor belts, production lines , machine tool industries progressive assembly lines , automatic handling apparatus where increased electrical and mechanical protection are required..

The copper screening assures a disturbance-free data and signal transmission for measuring and control systems.

Cross section with 1.5:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Insulation thickness

mm

No.cores xNominal cross section

mm

No.cores xNominal cross section

mm2

900 12.6 12.1/12.1 21.0 1.8 1.25 0.8 7*1.5+1.5
920 12.6 12.1/7.41 21.3 1.8 1.25 0.8 7*1.5+2.5
1110 11.7 12.1/7.41 22.7 1.8 1.6 0.8 8*1.5+2.5
1320 10.7 12.1/7.41 25.0 1.8 1.6 0.8 10*1.5+2.5
1390 10.1 12.1/7.41 25.5 1.8 1.6 0.8 12*1.5+2.5
1450 9.7 12.1/7.41 26.0 1.8 1.6 0.8 14*1.5+2.5
1550 9.1 12.1/4.61 27.0 1.8 1.6 0.8 16*1.5+4
1700 8.7 12.1/4.61 28.0 1.8 1.6 0.8 19*1.5+4
1780 8.3 12.1/3.08 29.5 1.9 1.6 0.8 21*1.5+6
2050 7.8 12.1/3.08 31.7 1.9 1.6 0.8 24*1.5+6
2250 7.2 12.1/3.08 33.0 2.0 1.6 0.8 30*1.5+6
2950 6.7 12.1/1.83 37.0 2.1 2.0 0.8 40*1.5+10
3450 6.2 12.1/1.83 40.5 2.2 2.0 0.8 52*1.5+10
3850 5.8 12.1/1.83 43.0 2.3 2.0 0.8 61*1.5+10

Cross section with 2.5:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Insulation thickness

mm

No.cores xNominal cross section

mm

No.cores xNominal cross section

mm2

1260 16.9 7.41/7.41 23.0 1.8 1.6 0.8 7*2.5+2.5
1300 15.6 7.41/7.41 24.3 1.8 1.6 0.8 8*2.5+2.5
1550 14.3 7.41/4.61 27.0 1.8 1.6 0.8 10*2.5+4
1660 13.5 7.41/4.61 27.5 1.8 1.6 0.8 12*2.5+4
1760 13.0 7.41/4.61 28.2 1.8 1.6 0.8 14*2.5+4
1780 13.0 7.41/3.08 28.5 1.8 1.6 0.8 14*2.5+6
1920 12.2 7.41/3.08 30.0 1.9 1.6 0.8 16*2.5+6
2070 11.7 7.41/3.08 31.0 1.9 1.6 0.8 19*2.5+6
2300 11.4 7.41/1.83 32.8 2.0 1.6 0.8 21*2.5+10
2810 10.4 7.41/1.83 36.0 2.1 2.0 0.8 24*2.5+10
3110 9.6 7.41/1.83 37.5 2.1 2.0 0.8 30*2.5+10
3520 9.1 7.41/1.83 41.0 2.2 2.0 0.8 40*2.5+10
4330 8.3 7.41/1.83 45.0 2.4 2.0 0.8 52*2.5+10
5220 7.8 7.41/183 48.5 2.5 2.5 0.8 61*2.5+10