Technical data:
- Power cable according to IEC 60502-1 , DIN VDE 0271 , BS 5467
- Temperature range:
during installation up to C°-5
Operating temperature: Max C°+90
Short circuit. temperature: C°+250
- Nominal voltage: U0/U=0.6/1 KV
- Test voltage a.c. ,50Hz: 4 KV
Cable structure:
- AL / XLPE / PVC / PVC
- Aluminium conductor class1 or 2 acc. to IEC 60228
- Insulation XLPE
- Sheath PVC/ST2 90°C
Application:
Power cables for energy supply are installed in underground , in water , indoors , in cable ducts , power stations , for industry and distribution boards as well as in subscriber.
Single core:
Approx. Current kg/km |
Current capacity in air C°30 (A) |
Max. resistance at C°20 (Ω/KM) |
Overall dimensions mm |
Sheath thickness mm |
Insulation thickness mm |
No.cores xNominal cross section mm2 |
117 | 70 | 1.91 | 9.6 | 1.4 | 0.7 | 1*16 |
162 | 120 | 1.20 | 11.3 | 1.4 | 0.9 | 1*25 |
200 | 163 | 0.868 | 12.4 | 1.4 | 0.9 | 1*35 |
263 | 200 | 0.641 | 14.0 | 1.4 | 1.0 | 1*50 |
347 | 254 | 0.443 | 16.0 | 1.4 | 1.1 | 1*70 |
442 | 313 | 0.320 | 18.0 | 1.5 | 1.1 | 1*95 |
553 | 366 | 0.253 | 19.7 | 1.6 | 1.2 | 1*120 |
666 | 420 | 0.206 | 21.9 | 1.6 | 1.4 | 1*150 |
841 | 486 | 0.164 | 24.2 | 1.7 | 1.6 | 1*185 |
1039 | 585 | 0.125 | 27.0 | 1.8 | 1.7 | 1*240 |
1311 | 675 | 0.100 | 29.6 | 1.9 | 1.8 | 1*300 |
1602 | 798 | 0.0778 | 33.2 | 2.0 | 2.0 | 1*400 |
2050 | 926 | 0.0605 | 36.8 | 2.1 | 2.2 | 1*500 |
3 Cores:
Approx. Current kg/km |
Current capacity in air C°30 (A) |
Max. resistance at C°20 (Ω/KM) |
Overall dimensions mm |
Sheath thickness mm |
Insulation thickness mm |
No.cores xNominal cross section mm2 |
715 | 147 | 0.641 | 26.0 | 1.8 | 1.0 | 3*50sm |
970 | 189 | 0.443 | 28.0 | 1.8 | 1.1 | 3*70sm |
1250 | 232 | 0.320 | 31.0 | 1.9 | 1.1 | 3*95sm |
1540 | 270 | 0.253 | 36.0 | 2.0 | 1.2 | 3*120sm |
1865 | 308 | 0.206 | 38.0 | 2.1 | 1.4 | 3*150sm |
2332 | 257 | 0.164 | 41.0 | 2.2 | 1.6 | 3*185sm |
2975 | 435 | 0.125 | 47.0 | 2.3 | 1.7 | 3*240sm |
3666 | 501 | 0.100 | 55.0 | 2.6 | 1.8 | 3*300sm |
3.5 Cores:
Approx. Current kg/km |
Current capacity in air C°30 (A) |
Max. resistance at C°20 (Ω/KM) |
Overall dimensions mm |
Sheath thickness mm |
Insulation thickness mm |
No.cores xNominal cross section mm2 |
873 | 147 | 0.641/1.20 | 27.0 | 1.8 | 1.0/0.9 | 3*50/25 |
1200 | 189 | 0.443/0.868 | 30.8 | 1.9 | 1.1/0.9 | 3*70/35 |
1522 | 232 | 0.320/0.641 | 35.0 | 2.0 | 1.1/1.0 | 3*95/50 |
1915 | 270 | 0.253/0.443 | 38.0 | 2.1 | 1.2/1.1 | 3*120/70 |
2280 | 308 | 0.206/0.443 | 42.1 | 2.3 | 1.4/1.1 | 3*150/70 |
2875 | 357 | 0.164/0.320 | 46.8 | 2.4 | 1.6/1.1 | 3*185/95 |
3664 | 435 | 0.125/0.253 | 52.5 | 2.6 | 1.7/1.2 | 3*240/120 |
4452 | 501 | 0.100/0.206 | 58.0 | 2.8 | 1.8/1.4 | 3*300/150 |
4 Cores:
Approx. Current kg/km |
Current capacity in air C°30 (A) |
Max. resistance at C°20 (Ω/KM) |
Overall dimensions mm |
Sheath thickness mm |
Insulation thickness mm |
No.cores xNominal cross section mm2 |
953 | 147 | 0.641 | 28.0 | 1.8 | 1.0 | 4*50sm |
1258 | 189 | 0.443 | 33.0 | 2.0 | 1.1 | 4*70sm |
1653 | 232 | 0.320 | 37.0 | 2.1 | 1.1 | 4*95sm |
2075 | 270 | 0.253 | 40.0 | 2.2 | 1.2 | 4*120sm |
2511 | 308 | 0.206 | 44.2 | 2.3 | 1.4 | 4*150sm |
3136 | 357 | 0.164 | 49.0 | 2.5 | 1.6 | 4*185sm |
4016 | 435 | 0.125 | 55.0 | 2.6 | 1.7 | 4*240sm |
4942 | 501 | 0.100 | 60.0 | 2.8 | 1.8 | 4*300sm |