Power cable NYCYRY (wire armoured with concentric conductor)

 

Technical data:

- Power cable according to IEC 60502-1 , DIN VDE 0271 , ISIRI 3569

- Temperature range:

   flexing C°-5 to C°+50

   fixed installation C°-30 to C°+70

- Nominal voltage: U0/U=0.6/1 KV

- Test voltage a.c. , 50Hz : 4 KV

Cable structure:

- Cu / PVC / PVC / Cu / PVC / SWA / PVC

- Copper conductor class1 & 2 acc. to IEC 60228

- Insulation PVC/A

- Concentric conductor in inner layer of round copper wires ,outer layer with copper tape.

- Galvanised steel or aluminium wire armoured.

- Sheath  PVC/ST2 90°C

Application:

Power cables for energy supply are used for industry and distribution boards , power stations and house connecting boxes, Overall , where increased elcctrical and mechanical protection are required. Those cables are installed in underground .in water, indoors and in cable ducts.

The concentric conductor (c) is allowed to use an neutral, protective or earthed conductor. For single core cables aluminum armuour is recommended.

2.5 Cores:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Wire Armour

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

625 19.5 12.1/12.1 18.0 1.8 1.25 0.8 2*1.5+1.5
710 26 7.41/7.41 19.0 1.8 1.25 0.8 2*2.5+2.5
870 34 4.61/4.61 21.0 1.8 1.25 1.0 2*4+4
970 44 3.08/3.08 21.7 1.8 1.25 1.0 2*6+6
1360 60 1.83/1.83 25.0 1.8 1.6 1.0 2*10+10
1770 80 1.15/1.15 28.4 1.8 1.6 1.0 2*16+16

3.5 Cores:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Wire Armour

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

661 19.5 12.1/12.1 18.5 1.8 1.25 0.8 3*1.5+1.5
760 26 7.41/7.41 19.5 1.8 1.25 0.8 3*2.5+2.5
935 34 4.61/4.61 21.5 1.8 1.25 1.0 3*4+4
1200 44 3.08/3.08 23.1 1.8 1.6 1.0 3*6+6
1490 60 1.83/1.83 25.5 1.8 1.6 1.0 3*10+10
1985 80 1.15/1.15 30.0 1.9 1.6 1.0 3*16+16
2770 108 0.727/1.15 34.0 2.0 2.0 1.2 3*25+16
2910 108 0.727/0.727 35.0 2.1 2.0 1.2 3*25+25
3110 132 0.524/1.15 36.0 2.1 2.0 1.2 3*35+16
3380 132 0.524/0.524 37.5 2.1 2.0 1.2 3*35+35
3450 160 0.387/0.727 37.5 2.1 2.0 1.4 3*50+25
3750 160 0.387/0.387 39.0 2.1 2.0 1.4 3*50+50
4350 202 0.268/0.524 41.0 2.2 2.0 1.4 3*70+35
4800 202 0.268/0.268 43.0 2.3 2.0 1.4 3*70+70
5600 249 0.193/0.387 46.0 2.3 2.0 1.6 3*95+50
6000 249 0.193/0.193 46.2 2.3 2.0 1.6 3*95+95
7000 289 0.153/0.268 49.0 2.4 2.5 1.6 3*120+70
7550 289 0.153/0.153 50.5 2.5 2.5 1.6 3*120+120
8250 329 0.124/0.268 55.0 2.6 2.5 1.8 3*150+70
9000 329 0.124/0.124 56.0 2.6 2.5 1.8 3*150+150
9850 377 0.0991/0.193 59.0 2.7 2.5 2.0 3*185+95
12220 443 0.0754/0.153 65.0 2.9 2.5 2.2 3*240+120

4.5 Cores:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Wire Armour

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

720 19.5 12.1 19.2 1.8 1.25 0.8 4*1.5+1.5
840 26 7.41 20.5 1.8 1.25 0.8 4*2.5+2.5
1170 34 4.61 23.3 1.8 1.6 1.0 4*4+4
1350 44 3.08 25.0 1.8 1.6 1.0 4*6+6
1690 60 1.83 27.5 1.8 1.6 1.0 4*10+10
2250 80 1.15 31.5 1.9 1.6 1.0 4*16+16

5.5 Cores:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Wire Armour

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

790 14.6 12.1 20.0 1.8 1.25 0.8 5*1.5+1.5
910 19.5 7.41 21.5 1.8 1.25 0.8 5*2.5+2.5
1280 25.5 4.61 25.0 1.8 1.6 1.0 5*4+4
1500 33.0 3.08 26.4 1.8 1.6 1.0 5*6+6
1900 45.0 1.83 29.0 1.9 1.6 1.0 5*10+10
2800 60.0 1.15 34.7 2.0 2.0 1.0 5*16+16

4:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Wire Armour

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

1400 22.1 4.61 26 1.8 1.6 1.0 7*4+4
1670 28.6 3.08 28 1.8 1.6 1.0 7*6+6

end faq