Light PVC flat cable with protective conductor 300/500 V

 

Technical data :

- PVC insulated, PVC sheated flat cables

with circuit protective conductor as BS 6004

- Nominal voltage: U0/U=300/500 V

- Colors for core identification:

  Single : red or black

  Twin : red and black

  3-Core :red ,yellow(center core) and blue

Cable structure:

- Cu / PVC / PVC

- Plain annealed copper conductor class 1 or 2 as me 60228

- PVC insulation type TI 1

- Parallel circuit protective bare conductor

- sheath :gray or white PVC

- (with two cores. the earth conductor is placed between black and red cores and for three cores, the earth is placed hetween blue and yellow cores).

Application:

These cables are used in internal wiring for power and lighting.

Permanent installation can be under and over and also within plaster.Laying in the ground is not permissible.

Single Core:

Current capacity in air C°30

(A)

Approx. Current

kg/km

Overall dimensions

mm

Sheath thickness

mm

Insulation thickness

mm

Class of conductors

 

No.cores xNominal cross section

mm2

25 40 4.1*5.3 0.9 0.6 1 1*1.0+1.0
40 49 4.6*5.7 0.9 0.7 1 1*1.5+1.0

Double-Cores:

Current capacity in air C°30

(A)

Approx. Current

kg/km

Overall dimensions

mm

Sheath thickness

mm

Insulation thickness

mm

Class of conductors

 

No.cores xNominal cross section

mm2

16 68 4.2*7.6 0.9 0.6 1 2*1.0+1.0
25 85 4.6*8.5 0.9 0.7 1 2*1.5+1.0
35 127 5.4*9.9 1.0 0.8 1 2*2.5+1.5
45 170 5.6*11.7 1.0 0.8 2 2*4+1.5
56 235 7.0*13.5 1.1 0.8 2 2*6+2.5
75 382 8.5*17.1 1.2 1.0 2 2*10+4
100 545 9.7*20 1.3 1.0 2 2*16+6

3 Cores:

Current capacity in air C°30

(A)

Approx. Current

kg/km

Overall dimensions

mm

Sheath thickness

mm

Insulation thickness

mm

Class of conductors

 

No.cores xNominal cross section

mm2

16 90 4.2*10.5 0.9 0.6 1 3*1.0+1.0
25 115 4.6*11.5 0.9 0.7 1 3*1.5+1.0
35 171 5.4*13.6 1.0 0.8 1 3*2.5+1.0
45 241 6.4*16.3 1.1 0.8 2 3*4+1.5
56 325 7.0*18.5 1.1 0.8 2 3*6+2.5
75 525 8.5*23.5 1.2 1.0 2 3*10+4
100 762 9.7*27.5 1.3 1.0 2 3*16+6

end faq