Power cable NYRY (wire armoured) 0.6/1 KV

 

Technical data:

- Power cable according to IEC 60502-1 , DIN VDE 0271 , ISIRI 3569

- Temperature range:

   flexing C°-5 to C°+50

   fixed installation C°-30 to C°+70

- Nominal voltage: U0/U=0.6/1 KV

- Test voltage: 4KV a.c. 50Hz

Cable structure::

- Cu / PVC / PVC /SWA / PVC

- Copper conductor class 1 or 2 acc. to me 60228

- Insulation PVC/A

- Galvanised steel or aluminium wire armoured

- Sheath  PVC/ST2 90°C

Application:

Power cables for energy supply can be installed in underground , in water , indoors , in cable ducts , power stations, for industry and distribution boards as well as in subscriber networks ,where mechanical damages are not to be expected •• for better mechanical protection armoured cables are used. For single core cables aluminium armour is recommended.

Single Core:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Wire Armour

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

340 81 1.83 14.5 1.8 0.9 1.0 1*10
415 107 1.15 15.5 1.8 0.9 1.0 1*16
600 144 0.727 18.0 1.8 1.25 1.2 1*25
690 176 0.524 19.0 1.8 1.25 1.2 1*35
850 214 0.387 20.2 1.8 1.25 1.4 1*50
1160 270 0.268 22.7 1.8 1.6 1.4 1*70
1460 334 0.193 25.0 1.8 1.6 1.6 1*95
1750 389 0.153 27.0 1.8 1.6 1.6 1*120
2100 446 0.124 28.5 1.8 1.6 1.8 1*150
2500 516 0.0991 31.0 1.9 1.6 2.0 1*185
3280 618 0.0754 35.0 2.0 2.0 2.2 1*240
4000 717 0.0601 38.0 2.1 2.0 2.4 1*300
4900 843 0.0470 42.0 2.2 2.0 2.6 1*400
6100 994 0.0366 45.0 2.4 2.0 2.8 1*500

Approx. weights for single core cables are basis of aluminium wire armouring

Available armouring with galvanised steel on request ( for D.C systems )

Double-Core:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Wire Armour

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

385 19.5 12.1 14.2 1.8 0.90 0.8 2*1.5
440 26 7.41 15.0 1.8 0.90 1.0 2*2.5
645 34 4.61 17.5 1.8 1.25 1.0 2*4
735 44 3.08 18.5 1.8 1.25 1.0 2*6
900 60 1.83 20.0 1.8 1.25 1.0 2*10
970 80 1.15 21.2 1.8 1.25 1.0 2*16
1770 108 0.727 27.5 1.8 1.60 1.2 2*25

Approx. weights for multi core cables are basis of galvanised steel wire armouring

3 Cores:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Wire Armour

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

415 19.5 12.1 15.0 1.8 0.9 0.8 3*1.5
480 26 7.41 15.5 1.8 0.9 0.8 3*2.5
705 34 4.61 18.0 1.8 1.25 1.0 3*4
815 44 3.08 19.1 1.8 1.25 1.0 3*6
1020 60 1.83 21.0 1.8 1.25 1.0 3*10
1530 80 1.15 25.0 1.8 1.6 1.0 3*16
2070 108 0.727 29.0 1.9 1.6 1.2 3*25
2380 132 0.524 30.5 1.9 1.6 1.2 3*35
2550 160 0.387 31.0 1.9 1.6 1.4 3*50sm
3600 202 0.268 35.0 2.0 2.0 1.4 3*70sm
4550 249 0.193 39.0 2.1 2.0 1.6 3*95sm
5400 289 0.153 41.5 2.2 2.0 1.6 3*120sm
6400 329 0.124 45.0 2.3 2.0 1.8 3*150sm
8150 377 0.0991 50.0 2.5 2.5 2.0 3*185sm
10200 443 0.0754 55.0 2.6 2.5 2.2 3*240sm
12900 504 0.0601 65.0 3.0 2.5 2.4 3*300sm

3.5 Corse:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Wire Armour

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

2250 108 0.727/1.15 32.5 1.9 1.6 1.2/1 3*25/16
2650 132 0.524/1.15 34.5 2.0 1.6 1.2/1 3*35/16
3300 160 0.387/0.727 36.0 2.0 2.0 1.4/1.2 3*50/25
4100 202 0.268/0.524 39.0 2.1 2.0 1.4/1.2 3*70/35
5300 249 0.193/0.387 44.0 2.3 2.0 1.6/1.4 3*95/50
6800 289 0.153/0.268 48.0 2.4 2.5 1.6/1.4 3*120/70
7980 329 0.124/0.268 52.0 2.6 2.5 1.8/1.4 3*150/70
9600 377 0.0991/0.193 56.5 2.7 2.5 2/1.6 3*185/95
12100 443 0.0754/0.153 63.5 2.9 2.5 2.2/1.6 3*240/120
14500 504 0.0601/0.124 70.0 3.1 2.5 2.4/1.8 3*300/150

Approx. weights for multi core cables are basis of galvanised steel wire armouring

4 Cores

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Wire Armour

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

460 19.5 12.1 15.6 1.8 0.90 0.8 4*1.5re
640 26 7.41 17.2 1.8 1.25 0.8 4*2.5re
820 34 4.61 19.5 1.8 1.25 1.0 4*4re
950 44 3.08 21.0 1.8 1.25 1.0 4*6re
1450 60 1.83 24.5 1.8 1.6 1.0 4*10rm
1820 80 1.15 27.0 1.8 1.6 1.0 4*16rm
2500 108 0.727 31.5 1.8 1.6 1.2 4*25rm
3100 132 0.524 34.5 2.0 2.0 1.2 4*35rm
3550 160 0.387 36.0 2.1 2.0 1.4 4*50sm
4550 202 0.268 41.0 2.2 2.0 1.4 4*70sm
4800 249 0.193 45.5 2.3 2.0 1.6 4*95sm
7350 289 0.153 49.5 2.5 2.5 1.6 4*120sm
8800 329 0.124 54.0 2.6 2.5 1.8 4*150sm
1066 377 0.0991 58.8 2.8 2.5 2.0 4*185sm
13500 443 0.0754 65.0 3.0 2.5 2.2 4*240sm
16100 504 0.0601 70.5 3.1 2.5 2.4 4*300sm

5 Cores

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resietance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Wire Armour

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

600 14.6 12.1 17.0 1.8 1.25 0.8 5*1.5
700 19.5 7.41 18.2 1.8 1.25 0.8 5*2.5
900 25.5 4.61 20.5 1.8 1.25 1.0 5*4
1200 33 3.08 22.5 1.8 1.6 1.0 5*6
1510 45 1.83 24.8 1.8 1.6 1.0 5*10
2090 60 1.15 29.5 1.9 1.6 1.0 5*16
3150 99 0.727 35.5 2.1 2.0 1.2 5*25

Approx. weights for multi core cables are basis of galvanised steel wire armouring

end faq