Control cable NYY (PVC insulated , PVC sheathed) 0.6/1 KV

 

Technical data:

- Power cable according to IEC 60502-1 , DIN VDE 0271 , ISIRI 3569

- Temperature range:

   flexing -5°C to +50°C

   fixed installation -30"C to +70"C

- Nominal voltage: U0/U=0.6/1 KV

- Test voltage: 4KV a.c. 50Hz

Cable structure:

- Cu / PVC / PVC

- Copper conductor classt & 2 acc. to IEC 60228

- Insulation PVC/A

- Sheath  PVC/ST2 90°C

Application:

As control and connecting cable in machines , conveyor belts ,production lines ,machine tool industries , progressive assembly lines , automatic handling apparatus for medium mechanical stress and for fixed installation but not suitable for open air.

Cross section with 1.5:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Insulation thickness

mm

No. core xNominal cross section

mm2

330 12.5 12.1 14.5 1.8 0.8 7*1.5
360 11.7 12.1 15.7 1.8 0.8 8*1.5
485 10.5 12.1 18.0 1.8 0.8 10*1.5
520 10 12.1 18.5 1.8 0.8 12*1.5
555 9.7 12.1 19.2 1.8 0.8 14*1.5
590 9.1 12.1 20.0 1.8 0.8 16*1.5
690 8.5 12.1 21.0 1.8 0.8 19*1.5
750 8.3 12.1 22.5 1.8 0.8 21*1.5
910 7.6 12.1 24.0 1.8 0.8 24*1.5
1036 7.2 12.1 25.5 1.8 0.8 30*1.5
1400 6.5 12.1 28.0 1.8 0.8 40*1.5
1655 6.2 12.1 32.0 1.9 0.8 52*1.5
1940 5.8 12.1 35.0 2.0 0.8 61*1.5

Cross section with 2.5:

Approx. weight

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall diameter

mm

Sheath thickness

mm

Insulation thickness

mm

No. core xNominal cross section

mm2

420 16.9 7.41 16.0 1.8 0.8 7*2.5
450 15.6 7.41 16.8 1.8 0.8 8*2.5
580 14.3 7.41 19.5 1.8 0.8 10*2.5
650 13.5 7.41 20.0 1.8 0.8 12*2.5
750 13.0 7.41 21.0 1.8 0.8 14*2.5
820 12.2 7.41 22.0 1.8 0.8 16*2.5
905 11.7 7.41 23.0 1.8 0.8 19*2.5
1060 11.4 7.41 23.8 1.8 0.8 21*2.5
1280 10.4 7.41 26.5 1.8 0.8 24*2.5
1450 9.6 7.41 28.0 1.8 0.8 30*2.5
1910 9.1 7.41 31.3 1.9 0.8 40*2.5
2400 8.3 7.41 37.0 2.1 0.8 52*2.5
2720 7.8 7.41 38.0 2.1 0.8 61*2.5