Technical Data:
- Power Cable according to ISIRI 607-10 , BS 6004 , VDE 0250 , IEC 60227
- Teamprature range:
Flexing C°-5 تا C°+50
Fixed installation C°-30 تا C°+70
- Nominal voltage: U0/U=300/500 V
- Test voltage: 2000V a.c. 50Hz
Cable structure:
- Cu / PVC / PVC
- Copper conductor classt & 2 acc. to IEC 60228
- nsulation PVC/C
- Sheath PVC/ST4
Application:
For industrial and wiring purposes,usable in the open ,in dry ,damp and wet environments in the open and concealed, as well as in masonry and in beton ,not suitable for imbedding in solidified or compressed-concrete. Outdoor usage is only possible, as long as the cable is protected against direct sunlight.
Double-cores:
Approx Weight kg/km |
Current Capacity in air 30 C |
Max resistance at C°20 (Ω/KM) |
Overall diameter mm |
Sheath thickness mm |
Insulation thickness mm |
No. of strands x dia mm |
No.cores xNominal cross section mm2 |
135 | 19.5 | 12.1 | 9.5 | 1.2 | 0.7 | 1*1.38 | 2*1.5 |
150 | 13.3 | 10.5 | 7*0.50 | ||||
175 | 26.0 | 7.4 | 11.0 | 1.2 | 0.8 | 1*1.78 | 2*2.5 |
200 | 8.0 | 11.5 | 7*0.67 | ||||
232 | 35.0 | 4.6 | 12.0 | 1.2 | 0.8 | 1*2.25 | 2*4 |
248 | 5.0 | 12.6 | 7*0.85 | ||||
295 | 46.0 | 3.1 | 12.9 | 1.2 | 0.8 | 1*2.76 | 2*6 |
315 | 3.3 | 13.6 | 7*1.04 | ||||
455 | 63.0 | 1.8 | 16.0 | 1.4 | 1.0 | 1*3.57 | 2*10 |
490 | 1.9 | 17.0 | 7*1.35 | ||||
670 | 87.0 | 1.2 | 19.0 | 1.4 | 1.0 | 7*1.70 | 2*16 |
985 | 115.0 | 0.8 | 22.5 | 1.4 | 1.2 | 7*2.14 | 2*25 |
1290 | 143.0 | 0.6 | 25.3 | 1.6 | 1.2 | 7*2.25 | 2*35 |
3 Cores:
Approx. weight kg/km |
Current capacity (A) in air C°30 (A) |
Max. resistance at C°20 (Ω/KM) |
Overall diameter mm |
Sheath thickness mm |
Insulation thickness mm |
No. of strands x dia mm |
No. cores xNominal cross section mm2 |
160 | 19.5 | 12.1 | 10.0 | 1.2 | 0.7 | 1*1.38 | 3*1.5 |
171 | 13.3 | 10.6 | 7*0.50 | ||||
215 | 26.0 | 7.4 | 11.3 | 1.2 | 0.8 | 1*1.78 | 3*2.5 |
23 | 8.0 | 12.0 | 7*0.67 | ||||
275 | 35.0 | 4.6 | 12..4 | 1.2 | 0.8 | 1*2.25 | 3*4 |
300 | 5.0 | 13.1 | 7*0.85 | ||||
370 | 46.0 | 3.1 | 14.0 | 1.4 | 0.8 | 1*2.76 | 3*6 |
398 | 3.3 | 14.8 | 7*1.04 | ||||
550 | 63.0 | 1.8 | 13.8 | 1.4 | 1.0 | 1*3.57 | 3*10 |
600 | 1.9 | 17.8 | 7*1.35 | ||||
840 | 87.0 | 1.2 | 20.0 | 1.4 | 1.0 | 7*1.70 | 3*16 |
1260 | 115.0 | 0.8 | 24.0 | 1.6 | 1.2 | 7*2.14 | 3*25 |
1620 | 143.0 | 0.6 | 26.8 | 1.6 | 1.2 | 7*2.25 | 3*35 |
4 Cores:
Approx. weight kg/km |
Current capacity (A) in air C°30 (A) |
Max. resistance at C°20 (Ω/KM) |
Overall diameter mm |
Sheath thickness mm |
Insulation thickness mm |
No. of strands x dia mm |
No. cores xNominal cross section mm2 |
190 | 17.5 | 12.1 | 10.8 | 1.2 | 0.7 | 1*1.38 | 4*1.5 |
200 | 13.3 | 11.1 | 7*0.50 | ||||
255 | 24.0 | 7.4 | 12.2 | 1.2 | 0.8 | 1*1.78 | 4*2.5 |
275 | 8.0 | 12.7 | 7*0.67 | ||||
350 | 32.0 | 4.6 | 13.5 | 1.4 | 0.8 | 1*2.25 | 4*4 |
370 | 5.0 | 14.5 | 7*0.85 | ||||
450 | 41.0 | 3.1 | 15.1 | 1.4 | 0.8 | 1*2.76 | 4*6 |
480 | 3.3 | 16.0 | 7*1.04 | ||||
685 | 57.0 | 1.8 | 18.0 | 1.4 | 1.0 | 1*3.57 | 4*10 |
735 | 1.9 | 19.2 | 7*1.35 | ||||
1030 | 76.0 | 1.2 | 21.9 | 1.4 | 1.0 | 7*1.70 | 4*16 |
1560 | 96.0 | 0.8 | 26.5 | 1.6 | 1.2 | 7*2.14 | 4*25 |
2030 | 135.0 | 0.6 | 29.2 | 1.6 | 1.2 | 7*2.25 | 4*35 |
5 Cores:
Approx. weight kg/km |
Current capacity (A) in air C°30 (A) |
Max. resistance at C°20 (Ω/KM) |
Overall diameter mm |
Sheath thickness mm |
Insulation thickness mm |
No. of strands x dia mm |
No. Cores x Nominal cross section mm2 |
220 | 17.5 | 12.1 | 11.3 | 1.2 | 0.7 | 11.38 | 5*1.5 |
230 | 13.3 | 12.0 | 7-0.50 | ||||
300 | 24.0 | 7.4 | 13.0 | 1.2 | 0.8 | 1*1.78 | 5*2.5 |
322 | 8.0 | 13.6 | 7*0.67 | ||||
412 | 32.0 | 4.6 | 15.0 | 1.4 | 0.8 | 1*2.25 | 5*4 |
440 | 5.0 | 16.0 | 7*0.85 | ||||
532 | 41.0 | 3.1 | 16.3 | 1.4 | 0.8 | 1*2.76 | 5*6 |
570 | 3.3 | 17.2 | 7*1.04 | ||||
810 | 57.0 | 1.8 | 19.6 | 1.4 | 1.0 | 1*3.57 | 5*10 |
876 | 1.9 | 21.0 | 7*1.35 | ||||
1260 | 76.0 | 1.2 | 24.4 | 1.6 | 1.0 | 7*1.70 | 5*16 |
1875 | 96.0 | 0.8 | 29.0 | 1.6 | 1.2 | 7*2.14 | 5*25 |
2485 | 135.0 | 0.6 | 32.6 | 1.6 | 1.2 | 7*2.25 | 5*35 |