Power cable N2XBY (tape armoured with XLPE insulation) 0.6/1 KV

 

Technical data:

- Power cable according to IEC 60502-1 , DIN VDE 0271 , ISIRI 3569

- Temperature range:

   during installation up to C°-5

   Operating temperature: Max C°+90

   Short circuit. temperature: C°+250

- Nominal voltage: U0/U=0.6/1 KV

- Test voltage a.c. ,50Hz: 4 KV

Cable structure:

- Cu / XLPE / PVC / DTA / PVC

- Copper conductor class1 or 2 acc. to IEC 60228

- Insulation XLPE

- Double tape Galvanised steel armoured

- Sheath  PVC/ST2 90°C

Application:

Power cables for energy supply are installed in underground , in water , indoors , in cable ducts , power stations ,for industry and distribution boards as well as in subscriber networks.

where mechanical damages are not to be expected, for better mechanical protection armoured cables are used. For single core cables aluminum armour is recommended

Single Core:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

285 96 1.83 12.7 1.8 0.5 0.7 1*10
375 128 1.15 14.2 1.8 0.5 0.7 1*16
500 173 0.727 16.0 1.8 0.5 0.9 1*25
590 212 0.524 17.0 1.8 0.5 0.9 1*35
740 258 0.387 18.2 1.8 0.5 1.0 1*50
965 328 0.268 20.0 1.8 0.5 1.1 1*70
1240 404 0.193 21.8 1.8 0.5 1.1 1*95
1520 471 0.153 23.8 1.8 0.5 1.2 1*120
1820 541 0.124 25.5 1.8 0.5 1.4 1*150
2200 626 0.0991 27.7 1.8 0.5 1.6 1*185
2820 750 0.0754 30.6 1.9 0.5 1.7 1*240
3470 864 0.0601 33.2 2.0 0.5 1.8 1*300
4350 1020 0.0470 36.7 2.1 0.5 2.0 1*400
5500 1173 0.0366 40.5 2.2 0.5 2.2 1*500

Approx. weights for single core cables are basis of aluminium tape armouring

Available armouring with galvanised steel on request (for D.C systems)

Double-Cores:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

252 24 12.1 12.6 1.8 0.2 0.7 2*1.5
300 32 7.41 13.3 1.8 0.2 0.7 2*2.5
360 42 4.61 14.2 1.8 0.2 0.7 2*4
430 53 3.08 15.2 1.8 0.2 0.7 2*6
555 73 1.83 17.0 1.8 0.2 0.7 2*10
795 96 1.15 20.0 1.8 0.2 0.7 2*16
1120 130 0.727 23.5 1.8 0.2 0.9 2*25

3 Cores:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

285 24 12.1 13.0 1.8 0.2 0.7 3*1.5re
335 32 7.41 13.8 1.8 0.2 0.7 3*2.5re
410 42 4.61 14.8 1.8 0.2 0.7 3*4re
500 53 3.08 15.9 1.8 0.2 0.7 3*6re
660 73 1.83 17.6 1.8 0.2 0.7 3*10rm
950 96 1.15 21.0 1.8 0.2 0.7 3*16rm
1350 130 0.727 24.8 1.8 0.2 0.9 3*25rm
1640 160 0.524 26.4 1.8 0.2 0.9 3*35rm
1850 195 0.387 27.2 1.8 0.2 1.0 3*50sm
2540 247 0.268 31.2 1.9 0.2 1.1 3*70sm
3420 305 0.193 34.0 2.0 0.2 1.1 3*95sm
4300 355 0.153 37.0 2.1 0.2 1.2 3*120sm
5500 407 0.124 41.0 2.2 0.5 1.4 3*150sm
6800 469 0.0991 44.8 2.3 0.5 1.6 3*185sm
8700 551 0.0754 50.0 2.5 0.5 1.7 3*240sm
10630

638

0.0601 60.0 2.8 0.5 1.8 3*300sm

Approx. weights for multi core cables are basis of galvanised steel tape armouring

3.5 Cores:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

1500 130 0.727/1.15 26.2 1.8 0.2 0.9/0.7 3*25/16
1850 160 0.524/1.15 28.0 1.8 0.2 0.9/0.7 3*35/16
2200 195 0.387/0.727 31.0 1.9 0.2 1.0/0.9 3*50/25
2900 247 0.268/0.524 34.4 2.0 0.2 1.1/0.9 3*70/35
4200 305 0.193/0.387 39.8 2.2 0.5 1.1/1.0 3*95/50
5200 355 0.153/0.268 43.0 2.3 0.5 1.2/1.1 3*120/70
6200 407 0.124/0.153 47.2 2.4 0.5 1.4/1.1 3*150/70
7600 469 0.0991/0.193 50.5 2.5 0.5 1.6/1.1 3*185/95
9800 551 0.0754/0.153 57.7 2.7 0.5 1.7/1.2 3*240/120
12050 638 0.0601/0.124 63.2 2.9 0.5 1.8/1.4 3*300/150

4 Cores:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

305 24 12.1 13.5 1.8 0.2 0.7 4*1.5re
372 32 7.41 14.5 1.8 0.2 0.7 4*2.5re
460 42 4.61 15.7 1.8 0.2 0.7 4*4re
570 53 3.08 16.9 1.8 0.2 0.7 4*6re
780 73 1.83 18.9 1.8 0.2 0.7 4*10rm
1135 96 1.15 22.8 1.8 0.2 0.7 4*16rm
1640 130 0.727 27.0 1.8 0.2 0.9 4*25rm
2000 160 0.524 28.9 1.9 0.2 0.9 4*35rm
2400 195 0.387 31.8 1.9 0.2 1.0 4*50sm
3270 247 0.268 36.6 2.1 0.2 1.1 4*70sm
4660 305 0.193 41.4 2.2 0.5 1.1 4*95sm
5700 355 0.153 44.7 2.3 0.5 1.2 4*120sm
6980 407 0.124 49.3 2.5 0.5 1.4 4*150sm
8520 469 0.0991 53.5 2.6 0.5 1.6 4*185sm
11000 551 0.0754 59.8 2.8 0.5 1.7 4*240sm
13500 638 0.0601 65.3 3.0 0.5 1.8 4*300sm

5 Cores:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

350 18 12.1 14.4 1.8 0.2 0.7 5*1.5
420 24 7.41 15.5 1.8 0.2 0.7 5*2.5
525 31.5 4.61 16.8 1.8 0.2 0.7 5*4
650 40 3.08 18.1 1.8 0.2 0.7 5*6
910 55 1.83 20.5 1.8 0.2 0.7 5*10
1330 72 1.15 24.6 1.8 0.2 0.7 5*16
1950 98 0.727 29.5 1.9 0.2 0.9 5*25
2410 120 0.524 32.0 2.0 0.2 0.9 5*35

Approx. weights for multi core cables are basis of galvanised steel tape armouring

end faq