Power cable N2XRY (wire armoured with XLPE insulation) 0.6/1 KV

 

Technical data:

- Power cable according to IEC 60502-1 , DIN VDE 0271 , ISIRI 3569 , BS 5467

- Temperature range:

   during installation up to C°-5

   Operating temperature: Max C°+90

   Short circuit. temperature: C°+250

- Nominal voltage: U0/U=0.6/1 KV

-Test voltage a.c. ,50Hz: 4 KV

Cable structure:

- Cu / XLPE / PVC / SWA / PVC

- Copper conductor class1 or 2 acc. to IEC 60228

- Insulation XLPE

- Galvanised steel or aluminium wire armoured

- Sheath  PVC/ST2 90°C

Application:

Power cables for energy supply are installed in underground , in water , indoors , in cable ducts , power stations ,for industry and distribution boards as well as in subscriber networks.

where mechanical damages are not to be expected, for better mechanical protection armoured cables are used. For single core cables aluminum armour is recommended

Single Core:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

207 60 4.61 12.0 1.8 0.9 0.7 1*4
236 75 3.08 12.5 1.8 0.9 0.7 1*6
290 95 1.83 13.3 1.8 0.9 0.7 1*10
385 128 1.15 14.8 1.8 0.9 0.7 1*16
550 173 0.727 17.2 1.8 1.25 0.9 1*25
640 212 0.524 18.0 1.8 1.25 0.9 1*35
790 258 0.387 19.3 1.8 1.25 1.0 1*50
1020 328 0.268 21.3 1.8 1.25 1.1 1*70
1350 404 0.193 23.7 1.8 1.6 1.1 1*95
1630 471 0.153 25.7 1.8 1.6 1.2 1*120
1920 541 0.124 27.3 1.8 1.6 1.4 1*150
2330 626 0.0991 29.7 1.9 1.6 1.6 1*185
2960 750 0.0754 32.6 2.0 1.6 1.7 1*240
3680 864 0.0601 35.8 2.1 2.0 1.8 1*300
4550 1020 0.0470 39.5 2.2 2.0 2.0 1*400
5690 1173 0.0366 43.0 2.3 2.0 2.2 1*500

Approx. weights for single core cables are basis of aluminium tape armouring

Available armouring with galvanised steel on request (for D.C systems)

Double-Cores:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

360 24 12.1 13.9 1.8 0.9 0.7 2*1.5
610 32 7.41 14.7 1.8 0.9 0.7 2*2.5
480 42 4.61 15.7 1.8 0.9 0.7 2*4
650 53 3.08 17.3 1.8 1.25 0.7 2*6
810 73 1.83 19.0 1.8 1.25 0.7 2*10
1220 96 1.15 22.8 1.8 1.6 0.7 2*16
1625 130 0.727 26.2 1.8 1.6 0.9 2*25

3 Cores:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

390 24 12.1 14.3 1.8 0.9 0.7 3*1.5re
450 32 7.41 15.2 1.8 0.9 0.7 3*2.5re
324 42 4.61 16.9 1.8 1.25 0.7 3*4re
730 53 3.08 18.0 1.8 1.25 0.7 3*6re
990 73 1.83 20.8 1.8 1.25 0.7 3*10rm
1400 96 1.15 23.8 1.8 1.6 0.7 3*16rm
1890 130 0.727 27.5 1.8 1.6 0.9 3*25rm
2300 160 0.524 29.3 1.9 1.6 0.9 3*35rm
2510 195 0.387 30.0 1.9 1.6 1.0 3*50sm
3250 247 0.268 32.5 2.0 1.6 1.1 3*70sm
4390 305 0.193 38.0 2.1 2.0 1.1 3*95sm
5250 355 0.153 41.0 2.2 2.0 1.2 3*120sm
6400 407 0.124 44.0 2.3 2.0 1.4 3*150sm
8020 469 0.0991 49.0 2.4 2.5 1.6 3*185sm
10150 551 0.0754 53.7 2.6 2.5 1.7 3*240sm
12350 638 0.0601 64.0 2.9 2.5 1.8 3*300sm

Approx. weights for multi core cables are basis of galvanised steel tape armouring

3.5 Cores:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

2080 130 0.727/1.15 31.0 1.9 1.6 0.9/0.7 3*25/16
2450 160 0.524/1.15 32.5 1.9 1.6 0.9/0.7 3*35/16
2860 195 0.387/0.727 34.2 2.0 1.6 1.0/0.9 3*50/25
3890 247 0.268/0.524 38.0 2.1 2.0 1.1/0.9 3*70/35
4950 305 0.193/0.387 42.5 2.2 2.0 1.1/10 3*95/50
5600 355 0.153/0.268 45.5 2.3 2.0 1.2/1.1 3*120/70
7520 407 0.124/0.268 51.0 2.5 2.5 1.4/1.1 3*150/70
9100 469 0.0991/0.193 56.0 2.7 2.5 1.6/1.1 3*185/95
11450 551 0.0757/0.153 62.0 2.9 2.5 1.7/1.2 3*240/120
13800 638 0.0601/0.124 67.0 3.0 2.5 1.8/1.4 3*300*150

4 Cores:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

430 24 12.1 15.0 1.8 0.9 0.7 4*1.5re
500 32 7.41 16.0 1.8 0.9 0.7 4*2.5re
700 42 4.61 17.8 1.8 1.25 0.7 4*4re
830 53 3.08 19.0 1.8 1.25 0.7 4*6re
1270 73 1.83 22.8 1.8 1.6 0.7 4*10rm
1630 96 1.15 25.4 1.8 1.6 0.7 4*16rm
2247 130 0.727 30.0 1.9 1.6 0.9 4*25rm
2800 160 0.524 31.9 2.0 1.6 0.9 4*35rm
3300 195 0.387 35.5 2.0 2.0 1.0 4*50sm
4300 247 0.268 40.5 2.2 2.0 1.1 4*70sm
5450 305 0.193 44.5 2.3 2.0 1.1 4*95sm
7100 355 0.153 49.0 2.4 2.5 1.2 4*120sm
8460 407 0.124 53.0 2.6 2.5 1.4 4*150sm
10130 469 0.0991 57.5 2.7 2.5 1.6 4*185sm
13020 551 0.0754 63.7 2.9 2.5 1.7 4*240sm
15500 638 0.0601 70.0 3.1 2.5 1.8 4*300sm

5 Cores:

Approx. Current

kg/km

Current capacity in air C°30

(A)

Max. resistance at C°20

(Ω/KM)

Overall dimensions

mm

Sheath thickness

mm

Tape Armour thickness

Φmm

Insulation thickness

mm

No.cores xNominal cross section

mm2

475 18 12.1 15.8 1.8 0.9 0.7 5*1.5
660 24 7.41 17.7 1.8 1.25 0.7 5*2.5
785 31.5 4.61 18.9 1.8 1.25 0.7 5*4
935 40 3.08 20.3 1.8 1.25 0.7 5*6
1445 55 1.83 24.5 1.8 1.6 0.7 5*10
1880 72 1.15 27.5 1.8 1.6 0.7 5*16
2630 98 0.727 32.5 2.0 1.6 0.9 5*25
3360 120 0.524 35.8 2.1 2.0 0.9 5*35

Approx. weights for multi core cables are basis of galvanised steel tape armouring

end faq