Technical data:
- Hard drawn copper with E-CU
- Standard:
BS 125 , DIN 48201
- Min. tensile strength: 400N/mm2
Cable structure:
- Stranded copper without annealing and sheath
Application:
Aerial power distribution
Hard drawn copper conductors:
Breaking load KN |
Approx. weight kg/km |
Overall diameter mm |
No.of strands xDia mm |
Conductor nominal cross section mm2 |
6.4 | 140 | 5.1 | 7*1.70 | 16 |
9.7 | 221 | 6.42 | 7*2.14 | 25 |
1.6 | 312 | 7.56 | 7*2.52 | 35 |
19.2 | 440 | 8.9 | 19*1.87 | 50 |
26.4 | 600 | 10.7 | 19*2.14 | 70 |
37.2 | 845 | 12.6 | 19*2.52 | 95 |
47.0 | 1047 | 14.2 | 37*2.03 | 120 |
58.7 | 1325 | 15.8 | 37*2.26 | 150 |